Low voltage
Due to the low catenary voltage in DC systems (1,5 or 3 kV) transmission
losses are high. This reduces the probability of having trains braking and
trains accelerating close enough to each other to allow for an effective
transmission considerably. Without additional technology to improve the
situation, substantial recovery rates can only be achieved in dense suburban
networks.
Voltage limits
It may happen that during braking the catenary voltage increases beyond the
limits foreseen by the standards. In this case voltage is automatically cut off
and no recovery is possible.
Feedback into supply grid
A feedback of recovered energy into the public grid is usually not an option
in DC systems. However, if substations are equipped with thyristor inverter
units , they become reversible and can feed energy into the supply
grid.
Insufficient braking power
The power of regenerative brakes is roughly the same as the one installed for
traction. For many situations (trains running late, bad track conditions,
unexpected stop signals) this is not sufficient. In this case regenerative
brakes are blended with dissipative brakes or completely replaced by them.
Generally, EMUs have a better regenerative braking performance than
loco-hauled trains, since more axles are powered. The higher the motor power and
the more axles are powered, the more energy may be recovered.
Acceptance
Acceptance is generally high. However some drivers are reported to be
reluctant to use regenerative brakes because of safety or timetable
concerns. |