   HTSC transformer  evaluated  
An innovative transformer concept based on ceramic high-temperature superconducting material instead of copper could considerably reduce transformer losses.
Technology field: Optimisation of traction technologies
close main section General information
  close sub-section Description
   

Principle

The main transformer accounts for a substantial share of traction losses. This is especially true in 16,7 Hz systems. An innovative transformer concept using ceramic high-temperature superconductors instead of copper as winding material could reduce the transformer losses almost to zero.

HTSC

Superconduction (the loss-free electric conduction properties of some materials at very low temperatures) was discovered in 1911. The superconductors known then were metallic and required cooling down to –269° C which was achieved only by expensive liquid helium. In 1986, ceramic materials were discovered having superconductive properties at much higher temperatures of about -196 °C. This temperature can be achieved by liquid nitrogen cooling allowing for a considerable reduction of costs and complexity of superconductor cooling.

Possible applications of HTSC aim at

  1. Optimisation of conventional equipment: motor, transformer, cable etc.
  2. Development of innovative equipment: magnetic energy storage, current limiter etc.

The transformer prototype made by Siemens

Siemens AG has developed two prototypes of HTSC transformers (a 100 kVA model and a 1 MVA demonstrator) in order to show principal feasibility for railway-relevant power classes.

The coils are made from Bi-2223 (Bi2Sr2Ca2Cu3O10) conductor tapes of 3 mm width and 0,3 mm thickness. These filaments of ceramic superconductors are embedded into a pure Ag or AgMg matrix and a jacket acting as an insulator in normal operation and providing a defined circuit in case of quenching (i.e. breakdown of superconduction). The coils are located around an iron core. The operating temperature of the transformer is 67 K (-206 °C). This temperature is produced by a surrounding cryostat based on liquid nitrogen (LN2) cooling.

Figure XXX shows the layout of the 1 MVA demonstrator.

Einscannen aus Weigel 2000!

General
Nominal output 1000 kVA
Frequency 50 Hz
Voltage 25 kV / 2 x 1.4 kV
Current 40 A / 2 x 360 A
Core
Height / width 1080 / 622 mm
Cross-section 329.8 cm2
Induction 1.7 T
Cryostat
Length (inside) 1140 mm
Width / height (inside)              832 / 420 mm
Winding (Bi-2223)
Diameter (HV/LV) 304 / 228, 382 mm            
Height 5000 mm

Source: Henning et al. 2000

Operational characteristics

Due to the time-consuming cool down process and the low permissible temperature gradient to ensure minimum material stresses, the HTSC transformer has to be kept at operating temperature even during standstill periods. For standstill of up to seven hours the thermal time constant is sufficient to maintain HTSC material at operating temperature. Beyond that the cooling system must be supplied either from catenary or from external supply.

Manufacturer

Siemens AG (in co-operation with DB AG) and others

close main section General criteria
  close sub-section Status of development: prototype
    R&D activities in various manufacturing companies. Siemens AG has built a 100 kVA model and a 1 MVA demonstration transformer. An on-board protoype is planned.
  Time horizon for broad application: in > 10 years
    If successfully tested, market introduction will be between 2005 und 2010 (according to Siemens AG).
  Expected technological development: highly dynamic
    (no details available)
    Motivation:
   
  • Energy saving
  • Mass and volume reduction
  Benefits (other than environmental): big
   

Mass and volume reduction

Siemens AG gives the following reductions in mass and volume:

 

 

Mass incl. cooling system

Volume of core-and-coil assembly

Conventional transformer

HTSC design

Conventional transformer

HTSC design

Regional rail

4800 kg

2200 kg

0,69 m3

0.36 m3

Locomotive

14500 kg

8700 kg

2.65 m3

2.33 m3

High-speed

9300 kg

5400 kg

1.6 m3

1.3 m3

Source: Weigel 2000.

  Barriers: high
   

Technological

HTSC transformers are not a mature technology yet. Technological uncertainties are medium.

Complexity

Especially the liquid nitrogen cooling system adds to the overall complexity of the transformer system and is a technology railways have no experience with.

Costs

Investment is high and maintenance costs are uncertain (as for all complex innovative technologies)

    Success factors:
    (no details available)
  Applicability for railway segments: high
    Type of traction:  electric - AC
    Type of transportation:  passenger - main lines, passenger - high speed, passenger - regional lines, passenger - suburban lines, freight
    „Sufficiently reliable designs“ (Siemens) are currently possible and planned for locomotives, high speed trains and regional MU trains. Application in freight trains is also discussed.
    Grade of diffusion into railway markets:
  Diffusion into relevant segment of fleet: 0 %
  Share of newly purchased stock: 0 %
    (no details available)
  Market potential (railways): highly uncertain
    If HTSC transformers become an accepted technology in railways, the corresponding market potential would be large. However, at present uncertainties are very high.
    Example:
    Prototypes developed at Siemens AG.
close main section Environmental criteria
  close sub-section Impacts on energy efficiency:
  Energy efficiency potential for single vehicle: 5 - 10%
  Energy efficiency potential throughout fleet: 2 - 5%
   

Siemens AG predicts the following efficiency improvements:

 

Efficiency at rated power

 

Conventional transformer

HTSC design

Regional rail

92 %

99,3 %

Locomotive

93 %

99,6 %

High-speed

92 %

99,7 %

Source: Weigel 2000

Although these values refer to rated load, it is assumed that the relative improvements are approximately true for all loads.

This yields the following elasticity table:

 

Traction

Brake energy recovery

Effect on efficiency of power train

Elasticity with regard to efficiency of power train

Effect on
total energy consumption for traction

High speed train

electric

No

8

1,00

8 %

 

 

Yes

8

1,11

9 %

Intercity train

electric

No

8

1,00

8 %

 

 

Yes

8

1,12

9 %

Regional train

electric

No

8

1,00

8 %

 

 

Yes

8

1,33

11 %

Suburban train

electric

No

8

1,00

8 %

 

 

Yes

8

1,42

11 %

Freight

electric

No

7

1,00

7 %

Range:

7 – 11 %

Source: IZT

These values refer to 16,7 Hz systems. For 50 Hz systems transformer losses are generally smaller and the effect of HTSC transformers on total energy consumption will be lower by 1 – 2 points giving a range of roughly 6 – 9 %.

Mass effects

The following gives an estimate of the order of magnitude of the secondary effects due to the reduced mass of the HTSC transformer:

  • High-speed train: The typical mass of a high-speed train is some 400 tons (ICE 2). According to Siemens the mass of a HTSC transformer of the high-speed power class is about 4 tons lower than for conventional transformer (cf. Benefits). This corresponds to 1 % mass reduction which translates into an almost negligible effect on total energy consumption of ~ 0,2 %.
  • Regional train: The typical mass of a regional train will be approx. 100-200 tons. The mass reduction due to the HTSC transformer will be ~ 2,6 tons (cf. Benefits) corresponding to ~ 1-3 % which corresponds to a reduction of total energy consumption of 1-2 %.

Total effect

Taking into account both mass and efficiency effects, one gets the following energy efficiency potential:

  • Main line and high-speed trains: 8 - 10 %
  • Suburban and regional trains: 9 - 13 %
  • Freight trains: 7 %

Standstill consumption

During standstill the power required for maintaining the system at operating temperature is in the order of 1,2 kW for a 1 MVA transformer. It is about three times higher if the main transformer is also used for auxiliaries during standstill. According to Siemens, energy costs for standstill will still be lower than for conventional transformers (cf. Infrastructure – running costs).

  Other environmental impacts: positive
   

Cooling agent

Liquid nitrogen is a cooling agent with less environmental impact than the oil used for cooling conventional transformers.

close main section Economic criteria
  close sub-section Vehicle - fix costs: high
    Siemens estimates initial investment costs to be double as high as for conventional 16,7 Hz train transformer. HTSC winding material is more expensive than conventional copper windings. Liquid nitrogen cooling systems are not yet in mass production.
  Vehicle - running costs: significant reduction
   

For an annual operation of 125.000 km, Siemens has calculated the following running costs for a regional train (German BR 424/425) with conventional and HTSC transformer (assuming an energy price of 0,06 Euro/kWh):

 

 

Maintenance costs

Energy costs

Total costs

Advantage of HTSC:

 

Euro/a

Euro/km

For  operation Euro/a

For standstill Euro/a

Euro/a

Euro/a

Conventional

2675

0,46

57050

4994

64719

 

HTSC

4225

0,36

45625

3587

53437

- 11282

Source: DB AG & Siemens AG (no year)

  Infrastructure - fix costs: low
    Maintenance requires infrastructure for supplying liquid nitrogen.
  Infrastructure - running costs: reduced
    Cooling system needs power supply even during stand-still periods. According to Siemens AG stand-still costs will amount to 3587 Euro/year (compared to 4994 Euro/year for conventional transformers) on regional line stock BR 424/425 and for 125000 km/year.
  Scale effects: high
    Being an innovative technology in the R&D stage, there will be large scale effects in case of market success. This refers to the HTSC transformer itself as well as to the cooling system.
  Amortisation: 2 - 5 years
    < 5 years according to Siemens AG.
close main section Application outside railway sector
  close sub-section Status of development outside railway sector: test series
    ABB has successfully tested a 630 kW-3phase HTSC transformer at a Swiss electric utility for one year under regular operational conditions.
  Time horizon for broad application outside railway sector: in > 10 years
    (no details available)
  Expected technological development outside railway sector: highly dynamic
    (no details available)
  Market potential outside railway sector: medium
    According to the International Superconductivity Industrial Summit, the worldwide market for superconductor-based products and systems will rise to 122 billion US Dollars by 2020. Market estimates for HTSC transformers only are not available.
close main section Overall rating
  close sub-section Overall potential: very promising
  Time horizon: long-term
    HTSC transformer is a highly promising long-term innovation for the electric traction system. Present R&D and prototypes promise high (50 Hz systems) to very high (16,7 Hz systems) energy efficiency effects. Remaining technological uncertainties are medium. According to manufacturers profitability is high enough to ensure reasonably fast payback of high initial costs. Maintenance and downtime costs are difficult to predict. Despite these uncertainties, HTSC transformers appear as a long-term option deserving intensive R&D efforts and further co-operation between railways and manufacturers.
References / Links:  DB AG & Siemens AG (no year);  Henning et al. (no year);  Hentschel et al. 2000;  Weigel 2000;  www.eren.doe.gov
Attachments:
Related projects:
Contact persons:
 date created: 2002-10-09
 
 
© UIC - International Union of Railways 2003
 